Measuring instruments


The portable tester G-Tester


for measuring of varistors mA point, DC ignition voltage of GDTs and insulating resistances

Simple portable diagnostic device designed for quick control of surge protection devices (SPD) containing metal oxide varistors and gas-filled surge arresters (GDT).

The device allows you to control:
a) The value of the so-called varistor voltage UV at 1 mA [V] for the SPD to 1000 V containing varistors.
b) The level of DC ignition voltage UVDC [V] for the SPD to 1000 V containing gas discharge tubes (GDT).
c) The value of an insulation resistance Riso (from 25 V DC up to 1000 V DC). 

Izolační odpory
Rozsah měření, jmenovitý rozsah měření 0,100   MΩ ÷ 1,999 GΩ   (U = 25 V ÷ 99 V)
     0,100 MΩ ÷ 3,999 GΩ (U = 100 V ÷ 249 V)
     0,100 MΩ ÷ 9,999 GΩ (U = 250 V ÷ 1000 V)
Rozlišovací schopnost 0,001 MΩ / 0,01   MΩ / 0,1 MΩ / 0,001 GΩ
Základní chyba měření ± (2% z MH +   10 D)* (R < 1 GΩ)
     ± (4% z MH + 15 D)* (R ≥ 1 GΩ)
Pracovní chyba měření ±   (3% z MH + 20 D)* (R < 1 GΩ)
     ± (5% z MH + 25 D)* (R ≥ 1 GΩ)
Jmenovitý měřicí proud ≥ 1 mA
Zkratový proud < 3 mA
Automatické   vybití měřeného objektu ano
Napětí ss a stř. (skutečná efektivní hodnota TRMS)
Rozsah měření UIn 0 V ÷ 600 V   ss / stř. (45 Hz ÷ 65 Hz)
Rozlišovací schopnost 1 V
Základní chyba měření ± (2% z MH +   2 D)*
Pracovní chyba měření ± (3% z MH +   3 D)*
Přepěťové ochrany
Rozsah měření 40 V ÷ 1050   V
Rozlišovací schopnost 1 V
Základní chyba měření ± (2% z MH +   2 D)*
Pracovní chyba měření ± (3% z MH +   3 D)*
Princip měření nárůst   napětí s měřením
     tzv. miliampérového bodu
Všeobecně
Napájení 4 ks AAA   (LR03) alkalická baterie 1,5 V nebo NiMH akumulátor 1,2 V
Displej OLED,   vícebarevný, grafický
Třída ochrany II (dvojitá   izolace)
Přepěťová kategorie CAT III /   300 V nebo CAT II / 600 V
Stupeň znečištění 2
Krytí IP43
Rozměry 260 x 70 x   40 mm
Hmotnost 0,36 kg
Katalogové číslo 99000

Buttons specification:

1) Ѻ - Key used to on (1x) or off (2x) device. If the device is switched on, you can briefly press the button to turn on (or off) light LEDs located on the front wall. 

2) Riso/USPD - Measuring mode selection button 
- Riso mode - in this mode it is necessary to preset setpoint max. measuring voltage using the buttons ↓ ↑ UTEST (can be adjusted 25, 50, 100, 250, 500 or 1000 V). After starting the measurement with the START button on the bottom right display shows the measured value Riso. 

SPD mode - in this mode takes place after the start of the measurement by pressing START testing non-linear element connected DC current of 1 mA. If the measured element is metal oxide varistor, the display shows the value of current through the SPD UV at 1 mA [V].If the measured component is the gas-filled surge arrester (GDT), the display shows the value its DC ignition voltage UVDC [V]. 

3) FUNC - Button enabling in mode USPD set minimum (DCmin) or maximum (DCmax) level transmitter mA point UV (in volts) for the so-called repeated measurements of the same type SPD. Setting these levels to the desired value using the buttons ↓↑ UTEST. 

Note: If the setting of levels DCmin and DCmax are done correctly, the test result SPD display text is either .... Test OK ....or TEST x