Surge arrester PSP */10/III


PSP */10/III

line discharge class 3

outdoor and indoor use

PSP */10/III – overvoltage limiters designed for protecting of high‑voltage transmission systems, transformers, switching equipment and HV cable distribution systems against atmospheric and switching overvoltage effects. The functional part of the limiters consists of a column of varistors sized for max. continuous operating voltage Uc . The outer insulating shell is made from silicon material (grey colour). The material of the shell shows high resistance to the effects of surface leakage currents and to electric arc, possesses hydrophobic properties and shows excellent resistance to weather effects, pollution and UV radiation. The cover caps, connecting screws, nuts and terminals are made of stainless steel. With their design and technical parameters, the overvoltage limiters of the PSP series conform to the standards EN 60099‑4: 2014 and IEC 60099‑4: 2014.

Type PSP 5/10/III PSP 7/10/III PSP 10/10/III PSP 12/10/III PSP 15/10/III PSP 18/10/III
Max. continuous operating voltage UC 4,8 kV 6,9 kV 9,9 kV 12 kV 15 kV 18 kV
Nominal voltage Ur 6 kV 8,6 kV 12,4 kV 15 kV 18,75 kV 22,5 kV
Nominal discharge current In 10 kA
High impulse current (4/10) 2 x 100 kA
Long current impulse (2 ms) 850 A
Discharge class acc. to EN 60099-4 3
Residual voltage at In Ures ≤ 17,7 kV ≤ 24,9 kV ≤ 35,6 kV ≤ 42,8 kV ≤ 53,5 kV ≤ 63 kV
Height h 130 mm 138 mm 168 mm 187 mm 216 mm 245 mm
Operating temperature range -40 °C ÷ + 55 °C
Protection type IP65
Weight m 2,9 kg 3,9 kg 4,4 kg 5 kg 5,4 kg 5,9 kg
Article number 96006 96007 96008 96009 96010 96011
Type PSP 22/10/III PSP 24/10/III PSP 29/10/III PSP 32/10/III PSP 36/10/III PSP 39/10/III
Max. continuous operating voltage UC 21,9 kV 24 kV 28,8 kV 31,8 kV 36 kV 39 kV
Nominal voltage Ur 27,4 kV 30 kV 36 kV 38,8 kV 45 kV 48,75 kV
Nominal discharge current In 10 kA
High impulse current (4/10) 2 x 100 kA
Long current impulse (2 ms) 850 A
Discharge class acc. to EN 60099-4 3
Residual voltage at In Ures ≤ 78,4 kV ≤ 85,6 kV ≤ 103,3 kV ≤ 114 kV ≤ 128,4 kV ≤ 139,1 kV
Height h 283 mm 303 mm 350 mm 379 mm 420 mm 450 mm
Operating temperature range -40 °C ÷ + 55 °C
Protection type IP65
Weight m 6,4 kg 7 kg 7,9 kg 8,4 kg 9 kg 9,4 kg
Article number 96012 96013 96015 96016 96017 96018

Note: The height and weight are indicative only and may vary. We can send accurate dat.

Application possibilities

Protection of high-voltage AC networks against lightning and switching surges and fast transients. Suitable for protection of transformers, cables, motors, switchgear, and other high-voltage equipment.

Advantages

• Long protective distance
• High absorption capacity
• Stable U-I characteristics even after repeated discharges
• Resistance to ageing
• Design resistant to explosion and bursting
• Resistance to pollution and UV radiation
• Resistance of the shell to rough handling
• Maintenance-free design
• Resistance to shocks and vibrations
• High mechanical resistance

Transport and storage

The overvoltage limiters may not be exposed to strong shocks and impacts during transport. They should be stored in the long term in an indoor store.

Maintenance

No testing of the function or maintenance such as cleaning is necessary during the anticipated life of the limiter.